The products that you selected had been put into inquiry basket !
Parâmetros
Características
Estrutura Chart
Pacote
Aplicação
Video
problema comum
FF 018 Filter Fan for Ventilation and Cooling
Axial fan, ball bearing
service life 50,000h at +25°C (+77°F), 65% RH fan body aluminium, rotor plastic
Connection
2 wires with pressure clamps 2.5mm², length 100mm
Casing (filter fan and exit filter)
plastic according to UL94 V-0, light grey
Hood (filter fan and exit filter)
plastic according to UL94 V-0, light grey; UV light resistant according to UL746C (f1)
Mounting frame
with double-sided industrial adhesive band for fixing to the outside of enclosure; certain operating circumstances can make the additional use of screws necessary (see drilling template); a template for the enclosure cut-out is included in the delivery of the filter fans
Filter mat
G4 acc. to DIN EN 779, filtering degree 94%
Filter material
synthetic fibre with progressive construction,temperature resistant to +100°C, self-extinguishing class F1,moisture resistant to 100% RH, reusable - cleaning by washing or vacuuming
Operating/Storage temperature
-10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F)
Operating/Storage humidity
max. 90% RH (non-condensing)
Enclosure cut-out
01800.0-00 / 01800.0-01: 97 x 97mm + 0.4 01800.1-00 / 01800.1-01: 125 x 125mm + 0.4 01800.2-00 / 01800.2-01: 176 x 176mm + 0.4
Protection class
IP55 / I (earthed)
Art. No.
Operating voltage
Air volume, free flow
Air volume with exit filter
Power consumption
Weight (approx.
01800.0-00
230VAC, 50Hz
21m³/h
16m³/h
16W
0.6kg
01801.0-00
230VAC, 50Hz
80m³/h
60m³/h
23W
1.0kg
01802.0-00
230VAC, 50Hz
90m³/h
70m³/h
23W
1.3kg
01800.0-01
120VAC, 60Hz
24m³/h
18m³/h
13W
0.6kg
01801.0-01
120VAC, 60Hz
63m³/h
48m³/h
15W
1.0kg
01802.0-01
120VAC, 60Hz
117m³/h
78m³/h
15W
1.3kg
¹ Using fine filter mats type F5/M5 increases the protection type to IP55, but reduces the air volume
EXIT FILTER EF 118
Art. No.
Depth in enclosure
Enclosure cut-out
Weight (approx.)
Filter mat
11800.0-00
16mm
97 x 97mm + 0.4
0.3kg
G4 acc. to DIN EN 779, filtering degree 94%
11801.0-00
16mm
125 x 125mm + 0.4
0.4kg
G4 acc. to DIN EN 779, filtering degree 94%
11802.0-00
16mm
176 x 176mm + 0.4
0.6kg
G4 acc. to DIN EN 779, filtering degree 94%
> Very low noise
> Minimal depth in enclosure
> Functional design
> Time-saving installation
> UV resistant
Fan filters are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localised hot pockets and protects the electronic components from overheating. These filter fans are intended for indoor use. The plastic used for the hood is highly UV light resistant.
Special features
> The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet.
> Functional design of the intake and exit fan hoods very effectively prevents direct intrusion of falling water and dust.
> The advantage is that the filter mat does not get so quickly contaminated with dirt and thus does not need to be exchanged so often.
> The air channeling makes the fan filter particularly quiet in operation.
> Functional and modern design enables time-saving assembly and maintenance.
> The direction of air flow can easily be switched by reversing the axial fan (sizes 1 to 3).
> EMC versions and other voltages on request.
Time-saving assembly and maintenance
Natural's fan filters are easily installed by one person from outside the cabinet.
1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and grease. A template for the enclosure cut-out is included in the delivery of the fan filter.
2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the cabinet opening. The frame stays permanently in the cabinet. (For size 176mm and up we recommend additional screw fixing.)
3.) Electrically connect the axial fan using the clip connectors. Push the unit into the mounting frame. Fix using screws.
4.) Insert the filter mat in the hood. Clip on. Finished.
Changing the filter mat or fan is quickly done by one person. To change the filter mat simply remove the filter hood, insert the new mat and snap the hood back again. No tools required. Maintenance of the fan can easily be done without removing the mounting frame (2).